Turbo ventilators are designed and engineered to exhaust Industrial pollutants such as smoke, dust, poisonous gases, humidity, fumes, heat and many more invisible irritants from the covered area. Turbo ventilator provides a safe, cool, healthier and more controlled environment by removing the entrapped heat and industrial emission ensuring the health of workers, thus contributing to an increase in workers productivity. Turbo Ventilators provide energy free cooling and fresh air through out the year.
This product is a Wind operated Turbo ventilator installed on the roof and is rotated by the Wind. The stale air inside is exhausted through the vanes and a natural inward flow of fresh air is boosted.Turbo Air ventilators works without electricity, it runs on wind velocity and it works 24 hours a day and 365 days a year This Turbo ventilator system functions and performs with the unlimited energy source like wind energy thus saving running cost of exhaust fans, wiring, maintenance etc.
Wind Turbo ventilators does not require operating time, it continuously rotate with the wind , removes moisture laden air in the winter and extremely hot air in the summer.
Technical Specifications
The wind influences the performance of the ventilator in two ways
- As the Wind approaches and strikes the ventilator, it jumps, creating an area of low pressure on the leeward side of the turbine, causing a continuous extraction of air from the building end
- As the turbine rotates, the centripetal forces associated with the rotation fling air outwards from the tips of the vanes. Replacement air is drawn into the throat of the ventilator from the building causing continuous ventilation.
Type of building | Air changes per Hour |
---|---|
Ware Houses | 3-5 |
Factories and workshops | 3-8 |
Assembly Halls | 6-12 |
Garages | 6-12 |
Toilets | 7-12 |
Laundries | 7-15 |
Poultry Houses | 7-25 |
Factories|(Heavy) | 20-40 |
The Ventilation Time for each area of the Building
Type of building | Time/Hour | Building | Time/hr |
---|---|---|---|
Machinery | 4-15 | Textile | 3-7 |
Forming | 10-30 | Dyeing | 10-40 |
Foundry | 10-30 | Repairing | 10-2 0 |
Electroplate | 12-20 | Washing | 10-30 |
Drying | 10-20 | Boiler | 15-30 |
Food | 3-8 | Lab | 6-15 |
Wood | 3-8 | Pump | 5-10 |
Paper | 8-15 |
Building | Time/Hour | Building | Time/hr |
---|---|---|---|
Library | 6-10 | Reception room | 4-12 |
Church | 6-10 | Toilet | 5-10 |
Classroom | 3-8 | WC | 4-14 |
Storehouse | 3-6 | Smoking room | 5-15 |
Car port | 4-10 | Restarunt | 6-12 |
Sickroom | 2-4 | House room | 5-10 |
Kitchen | 7-15 | Office | 2-5 |
Restroom | 10 | Sterillized room | 8-15 |
The Ventilating Cube of Metal TG-600
wind Speed(KM) | 3.2 | 6.4 | 8 | |||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|
Model | Turbine Diameter(MM) | Total Diameter(MM) | Room Height(M) | the ventilating cube per hour(M3) | ||||||||
Temperature Difference | 5 | 10 | 15 | 5 | 10 | 15 | 5 | 10 | 15 | |||
TG-600 | 720 | 600 | 3 | 1528 | 1716 | 1930 | 2076 | 2186 | 2314 | 2327 | 2510 | 2700 |
6 | 1712 | 1817 | 1986 | 2150 | 2360 | 2694 | 2766 | 2895 | 2895 | |||
9 | 1913 | 2190 | 2630 | 2659 | 3065 | 2956 | 3105 | 3348 | 3348 | |||
12 | 2065 | 2345 | 2700 | 2864 | 2925 | 3148 | 3188 | 3346 | 3468 |
wind Speed(KM) | 9.6 | 612.8 | 16.0 | |||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|
Temperature Difference | 5 | 10 | 15 | 5 | 10 | 15 | 5 | 10 | 15 | |||
Model | Turbine Diameter(MM) | Total Diameter(MM) | Room Height(M) | the vendilating cube per hour(M3) | ||||||||
TG-600 | 720 | 600 | 3 | 2720 | 2975 | 3070 | 3358 | 3565 | 3760 | 4033 | 4240 | 4357 |
6 | 2921 | 3158 | 3330 | 3547 | 3785 | 3961 | 4188 | 4430 | 4610 | |||
9 | 3150 | 3350 | 3535 | 3875 | 4161 | 4270 | 4518 | 4882 | 5050 | |||
12 | 3380 | 3786 | 3942 | 4215 | 4410 | 4656 | 4821 | 5125 | 5230 |